The Solo
The Solo is a single-loop analog-addressable fire control panel capable of driving up to 127 devices in 16 zones. Though small, the Solo is extremely powerful. Programmed by computer, it can be set up to control the activities of other systems (such as ventilation plant, door closers, public address, etc) as required to suit the needs of individual sites. Even without the computer it can be programmed with specific location and zone allocation information for each device so the cause of alarms and faults can be tracked down quickly and easilly, as well as simplifying commissioning and maintenance.
The use of a single 12 volt battery, (internally converted to 24 volts by the panel) promotes further cost savings and contributes to the compact and un-obtrusive design without affecting performance.
Advanced facilities include delayed alarms and automated day/night response switching. These help to reduce unwanted alarms by allowing the fire system to be customised to meet the specific needs of its environment.
 |
Key Features

· Supports loop-driven sounders
· Information displayed in clear language
· User-friendly controls activated by key-switch
· Cause-and-effect programming facility
· Optional printer or PC interface
· Optional fully-functional repeaters
· Compact design with flush mount option avaliable
· Supports Hochiki ESP loop protocol
· Apollo protocol version also available
· Complies with EN54 parts 2 & 4
|
Specifications
| Weight | 4Kg approximately (without battery). |
| Size | 250 x 330 x 88mm. Available in larger cabinet to special-order |
| Construction | Powdercoated 1.2mm sheet steel. Other finishes available to order. |
| Display | 2 line, 40 character LCD with yellow-green LED backlight. |
| Sounder outputs | 2 lines fused at 500mA each. Total 750mA maxi. |
| Auxiliary relays | Fire, Alarm & Fault, SPCO |
| Relay contact rating | 30v DC 1 amp maximum |
| Programmable outputs | 24, requires optional expansion card |
| Auxiliary supply | 24v DC 500mA |
| Remote Inputs | Alert, Evacuate, Fault, Silence & Reset |
| Number of Zones | 16 |
| Standby battery | 12v 7Ah SLA standard. Larger in optional large cabinet |
| Fuses | System - 5A 20mm. Charger - 350mA 20mm. Mains - 2A 20mm. |
| Mains supply | 220-240v AC 50Hz. 110v to special order. |
| Operating Temperature | -5 to +50° Centigrade |
| Operating humidity | <95%, non condensing |
Order Codes
| SOLO716 | Standard Hochiki protocol Solo fire control panel. Battery supplied seperately |
| BAT127 | 12v 7Ah battery |
Please contact us for ordering information relating to repeater, auxiliary relay card and special requirements.
|
|











 |