Sigma CP
The Sigma-CP conventional fire alarm control panel replaces the smaller panels of the K3000 range. It is suited to smaller systems requiring high performance and quality and has a newly designed, more stylish and easier to install enclosure. It is available with 2, 4 or 8 zones and conforms to the relevant European Standards. Repeaters and auxiliary relay units are available which connect via a simple two core RS485 interlink supporting multiple units, simplifying installation. All zones are fully programmable via panel controls to suit individual requirements, for a full list of program options please refer to the data sheet.
 |
Key Features

· Tested and certified to EN54-2 and EN54-4
· Easy to use with traditional key switch operation
· Compatible with BS5839 Part 1: 2002 installations
· 2-Wire repeaters and auxiliary modules available
· Fully programmable via panel controls
· Easy to install, “quick fit” chassis uses just 2 screws
· Simple, single board construction
· Compatible with most detection devices
· Class-change and remote control inputs
· 3 Amp power supply with auxiliary supply output
|
Specifications
| Size (WxHxD) | 385 x 310 x 90mm |
| Construction | 1.2mm mild steel |
| Colour | Lid/Back-box: mid grey. Chassis plate: light grey |
| Supply voltage | 200-250v AC 50Hz |
| Mains supply fuse | 1.6 amp 250v |
| DC power supply rating | 24 volt DC 3A |
| Battery size | 2x 12 volt 7Ah maximum |
| Auxiliary relays | Fire, Local Fire & Fault, SPCO |
| Relay contact rating | 30v DC 1 amp maximum |
| Alarm Line outputs | 2x 500mA each |
| Detection zone end-of-line | 6K8 0.5 watt (supplied). LCMU required for detector removal monitoring. |
| Alarm end-of-line | 10K 0.5 watt (supplied) |
| Maximum cable capacity | 2.5mm˛ per terminal |
| Operating temperature range | -5 to +50°C |
| Operating humidity | <95%, non condensing |
To enable detector removal monitoring, detector bases with continuity diodes must be used and the zones will require active end of line modules, supplied separately. Otherwise, detector bases must not be fitted with diodes and all manual call-points should be connected first before any detectors to comply with BS5839.
Order Codes
| K11020 | Sigma-CP panel, 2-zone, Batteries and LCMU sold separately. |
| K11040 | Sigma-CP panel, 4-zone, Batteries and LCMU sold separately. |
| K11080 | Sigma-CP panel, 8-zone, Batteries and LCMU sold separately. |
| K11LCMU | Sigma-CP LCMU active end of line module. |
| K11080R | Sigma-CP repeater panel, 8-zones, 24v DC powered. |
| K11MOD | Sigma-CP auxiliary relay module. |
|
|











 |