Hochiki Beam Detectors
Beam detectors are ideal for smoke detection within large areas such as warehouses, theatres, halls, etc, where conventional point detection is impractical or more costly. Because of their discreet design they are often used in places where architectural considerations are of importance.
The Reflective beam smoke detector consists of a wall-mounted reflector plate that faces a unit containing the Receiver & Emitter in one. It triggers a fire condition when the beam becomes obscured by smoke. The maximum distance between the plate and the detector is 30 metres.
For longer range detection, the 100m Detector consists of a wall-mounted emitter and receiver that face each other and convey a near-infrared beam. The receiver triggers a fire condition when the beam becomes obscured by smoke. The maximum distance between the two units is 100 metres and the smoke alarm threshold can be set to suit individual requirements.
 |
Key Features

· Sleek, unobtrusive units
· Easy installation and commissioning
· Automatic compensation for dirt & contamination
· Direct wall mounting prevents accidental misalignment
· Low power consumption, directly zone powered
· Detector removal monitoring
· Status indicators are easy to view from the ground
· Remote LED indicator output
· BS5839 approved
|
Installation & Location
Detectors should be located at a maximum of 7.5m from a wall and with a maximum of 15m between sets. Mounting height should be more than 80% of the ceiling height and more than 2.7m above the ground. The path between the emitter and receiver/detector unit and reflector plate should be permanently unobstructed and greater than 1m in diameter.
Beam alignment is initially achieved optically via sight holes that are viewed from the side of the detector. Once aligned, the reflective unit automatically sets up its reciever sensitivity, while the two-part system requires manual adjustment during commissioning. Both units will automatically adjust the sensitivity to compensate for dirt build-up on the lenses or gradual changes in atmospheric conditions.
The 100m Beam Detector (P11451) is supplied with mounting plates that fit onto British Standard double-gang electrical back boxes. The boxes must be at least 40mm deep and may be flush or surface mounted. Two cores are required interconnecting the emitter and reciever in addition to the zone wiring.
The 30m Reflective Beam Detector (P11840) is surface mounted via its own specially designed back box (P11906 – sold separately). The unit is self contained requiring only connection to the detection zone.
Full installation, setup and testing instructions are included with each set of beam detectors.
Specifications
| Unit | 100 meter 2-piece | 30 meter reflective |
| Size | Receiver & Emitter: 145x86x100 | Head unit: 152x112x80 Reflector: 190x190x3 Back box: 152x122x38 |
| Weight | Receiver: 0.7kg Emitter: 0.6kg | Head unit: 0.7kg Reflector: 0.05kg Back box: 0.5kg |
| Colour/Case material | Ivory ABS | Ivory ABS. Back-box powdercoated steel |
| Operating voltage | 15-33Vdc (Nominal rating 24Vdc) | 15-30Vdc (Nominal rating 24Vdc) |
| Stand-by current | 240µA at 24Vdc | 350µA at 24Vdc |
| Max. current in alarm | 50mA at 24Vdc | 50mA at 24Vdc |
| Operation range | 5 – 100m between emitter and receiver | 5 – 30m between detector and reflector |
| Sensitivity | Selectable - 25%, 50% & 70% obscuration | 30% obscuration |
| Compensation | 0.5% per 60mins (max) | 0.5% per 60mins (max) |
| Operating temp. | -10ºc to +50ºc | -10ºc to +50ºc |
| Maximum humidity | 95%RH – non condensing (at 40ºc) | 95%RH – non condensing (at 40ºc) |
Order Codes
| 11541 | 100 metre beam smoke detector set |
| 11840 | 30 metre reflective beam detector, requires back-box |
| 11906 | Back-box for 30 metre beam detector |
| 11768 | Beam Isolate Switch (custom made to order) |